Medium Voltage Soft Starter
Specifications
- Rated voltage
3.6 kV - 17.5 kV
- Rated busbar current
Up to 2000 A
- Rated short time withstand current / peak
Up to 40 kA for 1 second / 104 kA
- Internal arc fault IAC classification
AFL 31.5 kA for 1 second
- Loss of service continuity
LSC1 / LSC2 / LSC2B
- IP4X protection rating
(IP54 optional)
- Altitude
< 1000 m (higher with derating)
- Ambient temperature
-10 °C - 60 °C (above 50 °C with derating)
- Colour painting
RAL7035 (other colours optional)
L- Series MVE
MVE soft starters are a robust and reliable solution for your medium voltage starting needs.
Extensive personal safety features, an easy-to-use graphical interface, and comprehensive built-in motor/load protection make it a balanced solution for your medium voltage needs. MVE brings together advanced soft start motor control functionality in a robust yet compact physical configuration.
MVE is available as a fully furnished cabinet, or we can customize MVE into your existing system. MVE turn-key kit-type soft starters can be installed with minimal downtime. In addition to standard packages, we can provide a complete range to meet your needs.
Specifications
- Rated voltage
3.6 kV - 17.5 kV
- Rated busbar current
Up to 2000 A
- Rated short time withstand current / peak
Up to 40 kA for 1 second / 104 kA
- Internal arc fault IAC classification
AFL 31.5 kA for 1 second
- Loss of service continuity
LSC1 / LSC2 / LSC2B
- IP4X protection rating
(IP54 optional)
- Altitude
< 1000 m (higher with derating)
- Ambient temperature
-10 °C - 60 °C (above 50 °C with derating)
- Colour painting
RAL7035 (other colours optional)
Rely on MVE
Strong and reliable
Every application is different, and choosing the right starter for the job can sometimes seem like a daunting task. Variables such as altitude, ambient temperature, load and hourly starts all influence the selection of the ideal motor starting solution. At AuCom, we use sophisticated engineering tools to help you select the right MVE starter for your site conditions. Whatever the application, you can trust our experienced team of motor control professionals to get your motor running smoothly
TECHNICAL DATA
- Motor voltage
2.3 - 13.8 kV
- Control voltages
85 - 264 VAC or 90 - 350 VDC
- Frequency
45/66 Hz (autotrigger)
- Starter current
70 A - 1700 A
- tarting time (max)
1 Sec - 30 Sec (180 Sec)
- Ambient temperature
-10 ºC to 60 ºC (above 50 ºC with derating)
- Maximum altitude
1000 m (higher with derating)
- IP rating (controller)
IP54 / NEMA12
- CT type
Standard MV CTs (adjustable ratio)
- VT type
EPT type
- Isolasi MV/LV
100% fibre optic connection
- Digital input
3 fixed (start, stop, reset), 2 programmable (A, B)
- Relay output
4 fixed (line, bypass, PFC, PAPS), 3 programmable (A, B, C)
- Analog output
1 analog output
- Communications I/O
Modbus RTU, Modbus TCP, Profibus, Profinet, DeviceNet, Ethernet/IP, USB
Fully type tested
L-Series arc fault protection
Arc Fault
If an arc flash event occurs inside an AuCom L-Series panel, the arc flash disturbance is contained by the sturdy locking doors and heavy double-layer compartment panels.
During the emission phase, pressure is safely released using the discharge flap at the top of the panel (or optional chute), which directs the blast upwards or vents it safely to the outside.