Low Voltage Soft Starter
Low Voltage Soft Starter
Whether you need a full-featured motor control solution or a simple motor starter, AuCom has a product to suit. We cater to a wide range of user capabilities and feature sets. Your AuCom sales engineer's experience in a wide range of applications plus their motor control expertise will result in your Ideal AuCom Solution.
Beyond solutions, your sales engineer will also share their experience in many other projects similar to yours, to provide recommendations to maximize efficiency and deliver tangible results.
EMX4 Low Voltage Soft Starter
The EMX4i Soft Starter sets a new standard for soft start technology. Not only is the EMX4i smaller, more powerful, and equipped with new control and protection features, but it also introduces game-changing Smart Card capabilities. Attaching a Smart Card to the EMX4i transforms it from a super smart motor controller to a complete system controller.
Specifications
General
- Current Range
24 A ~ 1250 A (nominal)
- Motor connection
In-line or inside delta
- Bypass
Integrated internal
Supply
- Mains Voltage (L1, L2, L3)
EMX4i-xxxx-V5 200 VAC ~ 525 VAC (± 10%)
EMX4i-xxxx-V7 380 VAC ~ 690 VAC (± 10%)
EMX4i-xxxx-V12 1200 VAC (+10%/-20%) - Control Voltage (A1, A2, A3)
EMX4i-xxxxB-xx-C1 (A1, A2) 110 VAC ~ 120 VAC (+10%/-15%), 600 mA
EMX4i-xxxxB-xx-C1 (A2, A3) 220 VAC ~ 240 VAC (+10%/-15%), 600 mA
EMX4i-xxxxB-xx-C2 (A1, A3) 24 VAC/VDC (± 20%), 2.8 A - Mains Frequency
45 Hz to 66 Hz
- Form designation
Bypassed or continuous, semiconductor motor starter form 1
Short circuit capability
- Coordination with HRC fuses
Type 1
- Electromagnetic capability
(compliant with EU Directive 2004/108/EC)
- EMC Immunity
IEC 60947-4-2
- EMC Emissions
IEC 60947-4-2 Class B
Input
- Input rating
Active 24 VDC, 8 mA approx.
- Motor thermistor (B4, B5)
Trip >3.6kΩ, reset <1.6kΩ
Output
- Relay outputs
10 A @ 250 VAC resistive, 5 A @ 250 VAC, AC15 pf 0.3
- Main contactor (33, 34)
Normally open
- Relay output A (41, 42, 43)
Changeover
- Relay output B (53, 54)
Changeover
- Maximum load
600Ω (12 VDC @ 20 mA)
- Accuracy
± 5%
Environment
- Operating temperature
-10 °C ~ 60 °C, above 40 °C with derating
- Operating altitude
0 - 1000 m, above 1000 m with derating
- Storage temperature
-25 °C ~ 60 °C
- Humidity
5% to 95% Relative Humidity
- Pollution degree
Pollution Degree 3
- Vibration
IEC 60068-2-6
Heat dissipation
- During start
4.5 watts per ampere
- EMX4i-0024B ~ EMX4i-0052B
≤ 35 watts approx.
- EMX4i-0064B ~ EMX4i-0135B
≤ 50 watts approx
- EMX4i-0184B ~ EMX4i-0250B
≤ 120 watts approx.
- EMX4i-0352B ~ EMX4i-0580B
≤ 140 watts approx.
EMX3 Low Voltage Soft Starter
EMX3 is a comprehensive motor management system for the most demanding starting and stopping applications.
With an impressive range of features, including AuCom's innovative XLR-8 technology, the EMX3 delivers superior performance and an unprecedented level of flexibility in a compact, easy-to-use package.
The EMX3 is available as a chassis starter, in an enclosure as a standard package, or as a custom-designed solution.
Specifications
General
- Current Range
23 A ~ 1600 A (nominal)
- Motor connection
In-line or inside delta
- Bypass
Integrated internal or external
Supply
- Mains Voltage (L1, L2, L3)
EMX3-xxxx-V4 200 VAC ~ 440 VAC (± 10%)
EMX3-xxxx-V7 380 VAC ~ 690 VAC (± 10%) (in-line connection)
EMX3-xxxx-V7 380 VAC ~ 600 VAC (± 10%) (inside delta connection) - Control Voltage
(A1, A2, A3) 110 ~ 220 VAC (+ 10% / -15%)
or 230 ~ 440 VAC (+ 10% / -15%) - Mains Frequency
45 Hz to 66 Hz
Input
- Masukan
Active 24 VDC, 8 mA approx.
- Start (C23, C24)
Normally open
- Stop (C31, C32)
Normally closed
- Reset (C41, C42)
Normally open or closed
- Input A (C53, C54)
Normally open or closed
- Input B (C63, C64)
Normally open or closed
Output
- Relay outputs
10 A at 250 VAC resistive
5 A at 250 VAC, AC15 pf 0.3 - Run Relay (23, 24
Normally open
- Relay A (13, 14)
Normally Open
- Relay B (31, 32, 34)
Changeover
- Relay C (41, 42, 44)
Changeover
- Analog Output (B10, B11)
0-20 mA or 4-20 mA
- 24 VDC Output (P24, COM)
200 mA
Environment
- Operating temperature
-10 °C ~ 60 °C
- Storage temperature
- 10 °C ~ 60 °C
- Humidity
5% to 95% Relative Humidity